Commission & configure
Verification walk
Non-actuating WALK-260719-R1
Locations checked
183 / 400
Confirmed OK
181
Mismatches
2
Towers confirmed
3 / 8
Capture live
Scanner input is captured anywhere on this page — no need to click the field first.
No scans yet — scan a code.
Location map
31 OK 2 mismatch 17 pending
L001 L002 L003 L004 L005 L006 L007 L008 L009 L010 L011 L012 L013 L014 L015 L016 L017 L018 L019 L020 L021 L022 L023 L024 L025 L026 L027 L028 L029 L030 L031 L032 L033 L034 L035 L036 L037 L038 L039 L040 L041 L042 L043 L044 L045 L046 L047 L048 L049 L050
Mismatch at this tower
R1-T4-L012 Open
- Expected
- identity read at bus 2 addr 62 answers serial P9U-2604-0104 segment 12
- Observed
- segment 13 answered instead — neighbouring lamp lit on operator scan
- Suggested fix
- Swap the segment-12/13 harness plugs on tower 4 and re-check both locations
Mismatch at this tower
R1-T4-L031 Open
- Expected
- identity read at bus 2 addr 81 returns segment 31 status
- Observed
- no response within 3 retries (timeout 800 ms)
- Suggested fix
- Inspect tower-4 segment-31 connector; re-run tower after reseating